ASE2000 V1 Release Notes
ASE2000 Version 1 Release Notes
The ASE2000 Support Pages has added a specific section for Release notes. This list describes what has changed from one version to the next. Please note the table is organized from most recent release at the top, to the oldest on the bottom.
ASE2000 Version 1 Release Notes |
Release |
Details |
Date Released |
| Version 1.56 |
Area |
Protocol |
Comment |
New Features |
DNP3 LAN/WAN
|
Added option to specify UTC or local time |
USB Dongle Support |
Added support for USB Dongles with serial numbers U-3000 and higher, the ones used with ASE2000 Version 2 |
Corrections |
Harris 5000/6000 |
Corrected problem that can occasionally occur on line monitoring start-up, when master/slave communication is already active |
|
03-17-11 |
| Version 1.52 |
Area |
Protocol |
Comment |
New Features |
Southern Services |
Added support for Setpoint command |
BCOM-USB I/O Driver |
Added a signed driver for operation under Windows 7 64-bit mode |
File Locations under Windows 7 |
Under Windows 7, user files are located in a user data area instead of the ASE2000 Program Files installation folder. Files created by operation of a previous ASE2000 version are copied from the old location to the new location on installation of release 1.52. Some files may not be accessible by an older ASE2000 version after 1.52 is installed. |
Corrections |
IEC 870-5-101 and 104 |
Corrected Count field in transmission of Directory Call command from 0 to 1 |
Telegyr 6500 |
Corrected multi-point reporting |
Valmet (Tejas) series V 2-byte RTU |
Added LRC and CRC security options |
|
07-12-10 |
| Version 1.50 |
Area |
Protocol |
Comment |
New Features |
Modbus |
Added support for floating point values |
Added options to modify the work orders and/or byte ordering for two-word register values (long and floating point) |
IEC 870-5-104 |
Added support in the Point values view by specifying RTU ID 0 |
DNP3 |
Added ability to parse security messages in Monitor Mode |
Corrections |
DNP3 |
Corrected errors with UDP operation. This problem was introduced in 1.47 and did not exist in earlier releases. |
|
10-12-09 |
| Version 1.47 |
Area |
Protocol |
Comment |
New Features |
All |
Added support for a BCOM-USB device |
Corrections |
All |
Corrected error in line filtering. This version now supports the ability to display messages from/to a specific RTU only |
IEC 101 |
Corrected a problem with SBO sequences in balanced mode if the DIR bit is set in messages from the controlled to controlling station. In prior versions, the FCB bit would not change state between the select and execute steps. All other cases had, and still do, work OK. |
In RTU simulation mode, differentiate a response to a Delay Measurement message based on cause of transmission being Activate or Spontaneous |
Getac LP |
Corrected reporting ordering for DI points |
Telegyr 6500 |
Corrected interpretation of analog values |
SES-92 |
In RTU simulation mode, changed default return code for controls to indicate success |
|
04-30-09 |
| Version 1.46 |
Area |
Protocol |
Comment |
New Features |
DNP LAN/WAN |
Allow use of ports other than 20000 |
DNP |
Improved exchange matching logic to consider exchanges that differ only by qualifier information |
IEC 870-5-101 and 103 Slave |
Added option for Short Ack to replace No Data in response to Class 1 and Class 2 requests |
IEC 870-5-104 Master |
Allowed transmission of simulated point values in reverse direction |
IEC 870-5-101/104 Slave |
Limits number of points to those that can fit in one block |
Network |
Improved network card device detection to support more network cards |
Rockwell 5011 |
Added “Group” to point values view |
Binary and Generic Async |
Allowed editing of exchange properties |
Corrections |
Amtrak |
Improved exchange matching to allow for certain tag word bits to be set |
CDC Type 2 |
Corrected parsing of responses with an odd number of analog points |
Conitel 2025 |
Corrected parsing of Time Update message |
Conitel 2100H |
Increased re sync period to 15 milliseconds (it was 15 bits) |
DNP Master |
Corrected problem with SBO relay commands where the outstation response used Data Link confirm services |
Added parsing for re-transmitted Data Link frames |
Getac 7020-LP |
Corrected processing of inter-word gaps |
Getac 7024-BCH RTU Sim |
Corrected responses coded with an odd number of analogs |
Corrected abort when response to a CSEL contained a RENDX instead of just REND |
IEC 870-5-101/104 and DNP |
Do not issue execute portion of a SBO sequence after negative response to select |
IEC 870-5-104 |
Respond to TESTFR command even if STARTDT was not previously issued |
Indactic 33/41 |
Corrected security calculation error for measurand requests sent in extended addressing mode |
Line Analyzer |
Data collection used to trigger on a change in carrier signals. Added trigger on change in input data value, for use with constant carrier lines |
PG&E |
Added support for 13-bit analogs |
Telegyr 6500 |
Correct processing of responses with multiple pulse accumulator data blocks |
Changed interpretation of pulse data from LSB to MSB |
Added option to parse analog values with an inverted binary offset representation |
TRW System 9 Version B |
Corrected processing of multi-block data responses |
|
01-07-08 |
| Version 1.44 |
Area |
Protocol |
Comment |
New Features |
COM Port Version |
Added support for a USB dongle |
Corrections |
IEC 870-5-101 |
Improved processing confirmation of file ASDU types |
Corrected parse of Directory response |
SpaBus |
Added exchange for “Read Output Data” |
Raw Data Display |
Increased size of raw data viewing area to accommodate larger data blocks such as used for file transfer |
Amtrak |
Corrected processing of RR response for control actions |
|
04-12-06 |
| Version 1.43 |
Area |
Protocol |
Comment |
New Features |
All |
Issue warning when a “master simulation” session is started that includes an enabled relay control operation. User must acknowledge before proceeding |
Modbus |
When a holding register exchange is configured to request digital input data, the digital points are identified by bit positions 0 to 15 within each holding register address |
Corrections |
All |
Improve “stop on communication error” event processing. Prior releases may have stopped one message too late |
IEC 870-5-101 and 104 |
Change incorrect identification of ASDU Type 7 from unknown to Bit string |
IEC 870-5-103 |
Correct display of “Measurand 2” values in the Point Values view |
Identify “Invalid” bit when set in a time field |
Tejas 5 |
Correct calculation of starting index for status points |
TRW 9550 |
Fix parsing of responses longer than eight blocks |
|
12-13-05 |
| Version 1.42 |
Area |
Protocol |
Comment |
New Features |
Amtrak |
Add new protocol |
DNP3 |
Add capability to write multiple binary output points (object 10, variation 1) |
DNP3 and IEC |
Identify messages with no matching entry in the exchange list as “Unknown Exchange”. In the past, no exchange name was shown |
Corrections |
CDC Type 1 |
Correct display of CRC byte for Scan responses |
Conitel 2100H |
In the point values view, differentiate points in Status Group 1 from those in Status Group 2 |
DNP3 |
Correct RTU Simulation response to control output requests spanning more than one Data Link frame |
IEC 870-5-101/104 |
Process User Data [Confirm] response to control request in balanced/Master Simulation mode |
SC 1801 version 6 |
Correct processing of ‘L’ bit in SOE responses |
SpaBus |
Correct parsing of response messages |
|
08-11-05 |
| Version 1.41 |
Area |
Protocol |
Comment |
New Features |
DNP3 |
Added support for BCD (object 101) |
Added capability to send binary event with relative, un-synchronized, time |
Corrections |
Capture Files |
Corrected possible abort if a long capture file name was entered. Also corrects issue which occasionally required entering a full path for the file name (e.g., C:\temp\capture.cpt instead of just capture.cpt) |
DNP3 |
Corrected data link and application confirm processing to binary input event messages with relative time (Object 2, variation 3) |
Corrected occasional issue that would stop communication if a response was received from an DNP address other than as specified in the Exchange defaults menu |
Corrects transmission of Octet String objects |
IEC 870-5-103 |
Response to a General Command (ASDU type 20) has been corrected to be a Time Tagged Message (ASDU Type 1) |
Telegyr 6500 |
Corrects display of RTU number in Point Values view |
Telegyr 8979 |
- Corrected processor utilization problem when “A” and “B” cables were interchanged.
- Corrected processing of trip/close responses with exception blocks
|
|
05-18-05 |
| Version 1.40 |
Area |
Protocol |
Comment |
New Features |
All |
Removed support for ISA-bus BCOM2 card under Windows 2000 and
XP
|
Changed color of Point Values view to be more readable in sunlight
|
DNP3 |
Recognizes Data Set Object Groups
|
IEC 870-5-103 |
Added entry of Generic Command data set information for multiple data sets
|
Rockwell 5020 |
New protocol
|
Corrections |
All |
Corrected points values display for point indices 256 and greater
|
No longer required to un-check “Capture Enabled” option before viewing a capture file
|
Correctly capture file usage when name in a newly loaded configuration file is different from the default |
IEC 870-5-101 |
RTU Simulation Mode: Corrected balanced mode responses to general interrogation requests
|
IEC 870-5-103 |
Master Simulation Mode: Corrected Generic Command transmission when no data sets are defined |
IEC 870-5-104 |
RTU Simulation mode: Corrected common address values contained in responses to control output sequences |
Redac 70H |
Corrected parsing of 24-bit pulse accumulators
|
S/Comm 11.1 |
Fixed CRC positioning for long messages
|
Telegyr 8979 |
Corrected parsing of ADC responses with six points
|
Enhanced parsing of multiple block messages
|
Wisp+ |
Corrected interpretation of Digital Report exchange
|
|
11-12-04 |
| Version 1.39 |
| Area |
Protocol |
Comment |
| New Features |
DNP 3 |
Adds support for 2-bit digital input points (objects 3 and 4) |
| Obtains Virtual Terminal data from an external file, allowing entry of non-printable characters |
| Adds ForceError option to prevent Nack response to Data Link Confirm messages received before a Reset Link |
| IEC 870-5-104 |
In Master Simulation mode, restarts message transmission sequencing whenever the controlled station reconnects. This allows STARTDT to be transmitted on the initial connection and each subsequent re connection. |
| Adds “Step Position with Date/Time” exchange |
SPS |
Add support for Southwestern Public Services protocol |
| Corrections |
Capture Files |
Corrects read error for some large capture files |
| Conitel 2100H |
Inverts point identification for pass select and analog scan responses |
| DNP3 |
Corrects RTU Simulation-mode abort on reception of an Assign Class message |
| IEC 870-5-101 and IEC 870-5-104 |
Corrects problem reading messages with fewer octets than expected |
| IEC 870-5-103 |
Corrects cause of transmission code used in response to a General Command message |
| Network Protocols |
Corrects reading a protocol message arriving in multiple IP packets |
| Rockwell 501x |
Ignores state of unused bits in a data response header |
|
03-03-04 |
For more information about the products and services Applied Systems Engineering provides, select from
the main menu on the top or please feel free to contact
us directly if you have any questions or would like to discuss your
requirements with an application engineer.
Normal business hours are 9:00AM to 6:00PM Pacific Time, M - F.
Site Map | Search | About Us | Privacy | Contact Us
Applied Systems Engineering, Inc. 1671 Dell Avenue, Suite 200 Campbell, California 95008
Phone: (408) 364-0500 • Fax: (408) 364-0550 Email: products@ase-systems.com
Copyright ©2011 Applied Systems Engineering, Inc.
All rights reserved.